63.5 mm Rod Diameter Vertical Post insulator is usually used for the 69KV Usual System Voltage, and it is vertical clamp top line post insulator with the following drawing and specifications.
63.5 mm Rod Diameter Vertical Post insulator drawings:
63.5 mm Rod Diameter Vertical Post insulator specifications:
Catalog#
With 5” Bolt Circle&Vert. Clamptop
|
Usual System Voltage
(kV)
|
“X”
Length (mm)
|
No. Of Sheds
|
Dry Arc Distance (mm)
|
Leakage Distance (mm)
|
Low Freq. Flashover
(kV)
|
Critical Flashover
(kV)
|
RCL (kN)
|
Net Weigth (kg)
|
||
Dry
|
Wet
|
Pos.
|
Neg.
|
||||||||
01
|
69
|
780
|
8
|
584
|
1371
|
215
|
195
|
340
|
455
|
11.1
|
12.3
|
02
|
69
|
912
|
10
|
711
|
1727
|
270
|
245
|
420
|
535
|
11.0
|
13.6
|
63.5 mm Rod Diameter Vertical Post insulator is silicone rubber insulator, and used on high voltage transmission lines. RCL is the maximum cantilever continuous load at which the post insulators should be applied.