AS pin type insulators are widely used in the world, Orient Power designs and manufactures AS pin type insulators as per the following drawings and specifications or the requirements of customers.
AS pin type insulators for high voltage drawings:
AS pin type insulators for high voltage specifications:
Fig. No.
|
1
|
2
|
3
|
4
|
Nominal System Voltage/kV
|
SLP/11/180
|
ALP/11/275
|
ALP/22/450
|
ALP/22/490
|
Min. Nominal Creepage Distance/mm
|
180
|
275
|
450
|
490
|
Recommended Pin Type
|
A/130/7
|
C/150/7
|
C/200/11
|
C/200/11
|
Min. Cantilever Strength/kN
|
7
|
7
|
11
|
11
|
Power Frequency Withstand Voltage/kV
|
30
|
30
|
50
|
50
|
Lightning Impulse Withstand Voltage/kV
|
105
|
105
|
150
|
160
|
Power Frequency Puncture Voltage/kV
|
95
|
105
|
145
|
160
|
Weight/kg
|
1.50
|
3.2
|
3.8
|
4.2
|
Fig. No.
|
5
|
6
|
7
|
8
|
AS Class
|
ALP/22/480
|
ALP/22/520
|
ALP/33/710
|
ALP/33/920
|
Nominal System Voltage/kV
|
22
|
22
|
33
|
33
|
Min. Nominal Creepage Distance/mm
|
480
|
520
|
710
|
920
|
Recommended Pin Type
|
C/150/11
|
C/220/11
|
C/300/7
|
C/300/7
|
Min. Cantilever Strength/kN
|
11
|
11
|
11
|
11
|
Power Frequency Withstand Voltage/kV
|
50
|
50
|
90
|
90
|
Lightning Impulse Withstand Voltage/kV
|
150
|
150
|
220
|
220
|
Power Frequency Puncture Voltage/kV
|
130
|
160
|
210
|
220
|
Weight/kg
|
5.4
|
4.8
|
10.0
|
14.3
|