Fire wire and cable series will be introduced through standard, use occasions, produce name, type and use, Flame-retardant performance and Fire resistance level technical requirements.
Fire wire and cable standard:
Electrical performance products, like ordinary wire and cable, flame retardant, fire resistance in line with national standards GB/T18380-2001 (1EC60332: 1993), GB/T12666-1990 or national public safety industry standard GA306-2001 the requirements.
Fire wire and cable use occasions:
For a flame retardant, fire resistance, low smoke low halogen, low smoke zero halogen fire safety requirements, which are occasions, such as large-capacity power plants, nuclear power plants, subway, high-rise buildings, lots, and so densely populated.
Fire wire and cable produce name, type and use:
Name
|
Model
|
Level
|
Scope
|
Flame Retardant Series
|
ZR
|
IV A
|
35kv and below of AC rated voltage plastic insulated flame retardant power cables, AC rated voltage 450/750V and below flame-retardant plastic insulated control cable and AC rated voltage 450/750V and below flame-retardant plastic insulated cables
|
IV B
|
|||
IV C
|
|||
I A
|
|||
I B
|
|||
IC
|
|||
II A
|
|||
II B
|
|||
II C
|
|||
III A
|
|||
III B
|
|||
III C
|
|||
Fire Series
|
NH
|
I A
|
AC rated voltage plastic insulated fireproof power cables 0.6/1kV, AC rated voltage 450/750V and below the plastic insulation resistant control cable and AC rated voltage 450/750V and below the plastic insulation fire-resistant cables.
|
I B
|
|||
II A
|
|||
II B
|
|||
II A
|
|||
III B
|
|||
IV A
|
|||
IV B
|
Flame-retardant performance level technical requirements:
Flame retardant grade\ Project
|
Char height
|
Smoke toxicity (Concentration) mg/L
|
Smoke density (Minimum light transmittance)
%
|
||||
Test conditions
|
Technology Indicators
|
||||||
Volume of the sample non-metallic
L/m
|
Temperature in fire
℃
|
Time for fire min
|
|||||
Flame Ⅰ
|
I A
|
7.0
|
>815
|
40
|
≤2.5
|
≥12.4
|
≥80
|
I B
|
3.5
|
||||||
I C
|
1.5
|
20
|
|||||
Flame Ⅱ
|
II A
|
7.0
|
40
|
≥60
|
|||
IIB
|
2.5
|
||||||
II C
|
1.5
|
20
|
|||||
Flame Ⅲ
|
III A
|
7.0
|
40
|
≥6.15
|
≥20
|
||
III B
|
3.5
|
||||||
III C
|
1.5
|
20
|
|||||
Flame Ⅳ
|
IV A
|
7.0
|
|
40
|
|
-
|
-
|
IV B
|
3.5
|
||||||
IV C
|
1.5
|
20
|
|||||
Note:IV A、IV B、IV C Can be expressed as, respectively,A、B、C
|
Fire resistance level and technical requirements:
Flame retardant grade \ Project
|
Fire-resistant properties
|
Smoke toxicity (Concentration) mg/L
|
Smoke density (Minimum light transmittance)
%
|
||||
Test conditions
|
Technology Indicators
|
||||||
Sample applied voltage (U0/U)/V
|
Temperature in fire
℃
|
Time for fire min
|
|||||
Flame Ⅰ
|
I A
|
Voltage specified value of the product
|
950-1000
|
90
|
3A
Fuse inotblown
|
≥12.4
|
≥80
|
I B
|
750-800
|
||||||
Flame Ⅱ
|
II A
|
950-1000
|
≥60
|
||||
II B
|
750-800
|
||||||
Flame Ⅲ
|
III A
|
950-1000
|
≥6.15
|
≥20
|
|||
III B
|
750-800
|
||||||
Flame Ⅳ
|
IV A
|
950-1000
|
-
|
-
|
|||
IV B
|
750-800
|
Note:IV A, IV B Can be expressed as, respectively, A, B