Station post insulator drawings and specifications shown in the following are about ANSI standard type porcelain station post insulators. These insulators are only parts of Orient post insulators.
Station post insulator drawings:
Station post insulator specifications:
ANSI Class
|
286
|
287
|
-
|
|
Basic Impulse Insulation Level (KV)
|
550
|
550
|
550
|
|
Usual Line Voltage (KV)
|
115
|
115
|
115
|
|
Leakage distance/in (mm)
|
99(2515)
|
99(2515)
|
125(3175)
|
|
Cantilever Strength/Ib (KN)
|
1700(7.6)
|
2600(11.6)
|
1700(7.6)
|
|
Tensile Strength/Ib (KN)
|
20000(89)
|
25000(111.2)
|
20000(89)
|
|
Torsional Strength/in-Ib (N.m)
|
40000 (177.9)
|
90000(400.3)
|
40000(177.9)
|
|
Compression Strength /Ib (KN)
|
60000(266.9)
|
75000(333.6)
|
60000(266.9)
|
|
Critical Impulse Flashover Voltage, Positive (KV)
|
610
|
610
|
610
|
|
Withstand Voltage
|
Low Frequency, Wet/KV
|
230
|
230
|
230
|
Impulse/KV
|
550
|
550
|
550
|
|
Radio-Influence Voltage Data
|
Test Voltage to ground/kV
|
73
|
73
|
73
|
Maximum RIV at 1000 KHZ/µV
|
200
|
200
|
200
|
|
Height-“H”/in (mm)
|
45(1143)
|
45(1143)
|
45(1143)
|
|
Shed diameter/in (mm)
|
8-3/4(222)
|
8-7/8(225)
|
D1=9-1/4(235)
D2=7-11/16(195)
|
|
Bolt circle diameter/in (mm)
|
5(127)
|
5(127)
|
5(127)
|
|
(4)Tapped holes, size/in
|
5/8-11
|
5/8-11
|
5/8-11
|
|
Cap diameter-“C”/in (mm)
|
6-1/4(159)
|
6-1/4(159)
|
6-1/4(159)
|
|
Net Weight/Ib (kg)
|
142(63.2)
|
165(73.4)
|
154(68.5)
|
ANSI Class
|
288
|
289
|
-
|
|
Basic Impulse Insulation Level (KV)
|
650
|
650
|
650
|
|
Usual Line Voltage (KV)
|
116
|
116
|
116
|
|
Leakage distance/in (mm)
|
116(2946)
|
116(2946)
|
155(3937)
|
|
Cantilever Strength/Ib (KN)
|
1450(6.4)
|
2200(9.8)
|
1450(6.4)
|
|
Tensile Strength/Ib (KN)
|
20000(89)
|
25000(111.2)
|
20000(89)
|
|
Torsional Strength/in-Ib (N.m)
|
60000 (266.9)
|
90000(400.3)
|
60000(266.9)
|
|
Compression Strength /Ib(KN)
|
60000(266.9)
|
75000(333.6)
|
60000(266.9)
|
|
Critical Impulse Flashover Voltage, Positive (KV)
|
710
|
710
|
710
|
|
Withstand Voltage
|
Low Frequency, Wet/KV
|
275
|
275
|
275
|
Impulse/KV
|
650
|
650
|
650
|
|
Radio-Influence Voltage Data
|
Test Voltage to ground/kV
|
88
|
88
|
88
|
Maximum RIV at 1000 KHZ/µV
|
200
|
200
|
200
|
|
Height-“H”/in (mm)
|
54(1372)
|
54(1372)
|
54(1372)
|
|
Shed diameter/in (mm)
|
8-13/16(224)
|
10(254)
|
D1=9-1/4(235)
D2=7-11/16(195)
|
|
Bolt circle diameter/in (mm)
|
5(127)
|
5(127)
|
5(127)
|
|
(4)Tapped holes, size/in
|
5/8-11
|
5/8-11
|
5/8-11
|
|
Cap diameter-“C”/in (mm)
|
6-1/4(159)
|
6-1/4(159)
|
6-1/4(159)
|
|
Net Weight/Ib (kg)
|
160(71.2)
|
225(100)
|
170(75.6)
|
ANSI Class
|
291
|
295
|
-
|
|
Basic Impulse Insulation Level (KV)
|
750
|
750
|
750
|
|
Usual Line Voltage (KV)
|
161
|
161
|
161
|
|
Leakage distance/in (mm)
|
132(3353)
|
132(3353)
|
180(4572)
|
|
Cantilever Strength/Ib (KN)
|
1200(5.3)
|
1850(8.2)
|
1200(5.3)
|
|
Tensile Strength/Ib (KN)
|
20000(89)
|
25000(111.2)
|
20000(89)
|
|
Torsional Strength/in-Ib (N.m)
|
60000 (266.9)
|
90000(400.3)
|
60000(266.9)
|
|
Compression Strength /Ib (KN)
|
60000(266.9)
|
75000(333.6)
|
60000(266.9)
|
|
Critical Impulse Flashover Voltage, Positive (KV)
|
810
|
810
|
810
|
|
Withstand Voltage
|
Low Frequency, Wet/KV
|
315
|
315
|
315
|
Impulse/KV
|
750
|
750
|
750
|
|
Radio-Influence Voltage Data
|
Test Voltage to ground/kV
|
103
|
103
|
103
|
Maximum RIV at 1000 KHZ/µV
|
500
|
500
|
500
|
|
Height-“H”/in (mm)
|
62(1575)
|
62(1575)
|
62(1575)
|
|
Shed diameter/in (mm)
|
8-13/16(224)
|
10(254)
|
D1=9-1/4(235)
D2=7-11/16(195)
|
|
Bolt circle diameter/in (mm)
|
5(127)
|
5(127)
|
5(127)
|
|
(4)Tapped holes, size/in
|
5/8-11
|
5/8-11
|
5/8-11
|
|
Cap diameter-“C”/in (mm)
|
6-1/4(159)
|
6-1/4(159)
|
6-1/4(159)
|
|
Net Weight/Ib (kg)
|
170(75.6)
|
235(104.5)
|
195(86.7)
|
ANSI Class
|
304
|
308
|
308
|
|
Basic Impulse Insulation Level (KV)
|
900
|
900
|
900
|
|
Usual Line Voltage (KV)
|
230
|
230
|
230
|
|
Leakage distance/in (mm)
|
165(4191)
|
165(4191)
|
165(4191)
|
|
Cantilever Strength/Ib (KN)
|
950(4.2)
|
1450(6.4)
|
1450(6.4)
|
|
Tensile Strength/Ib (KN)
|
20000(89)
|
25000(111.2)
|
25000(111.2)
|
|
Torsional Strength/in-Ib (N.m)
|
60000 (266.9)
|
90000(400.3)
|
90000(400.3)
|
|
Compression Strength /Ib (KN)
|
60000(266.9)
|
90000(400.3)
|
75000(333.6)
|
|
Critical Impulse Flashover Voltage, Positive (KV)
|
1010
|
1010
|
1010
|
|
Withstand Voltage
|
Low Frequency, Wet/KV
|
385
|
385
|
385
|
Impulse/KV
|
900
|
900
|
900
|
|
Radio-Influence Voltage Data
|
Test Voltage to ground/kV
|
146
|
146
|
146
|
Maximum RIV at 1000 KHZ/µV
|
500
|
500
|
500
|
|
Shed diameter/in (mm)
|
9-1/2(241)
|
10-1/8(257)
|
D1=9-1/2(241)
D2=10-1/8(257)
|
|
Bolt circle diameter/in (mm)
|
5(127)
|
5(127)
|
5(127)
|
|
(4)Tapped holes, size/in
|
5/8-11
|
5/8-11
|
5/8-11
|
|
Cap diameter-“C”/in (mm)
|
6-1/4(159)
|
6-1/4(159)
|
6-1/4(159)
|
|
Net Weight/Ib (kg)
|
310(137.9)
|
375(166.8)
|
268(121.6)
|
Cat. No.
|
07011050-01
|
07011050-02
|
07011050-03
|
|
ANSI Class
|
312
|
316
|
362
|
|
Basic Impulse Insulation Level (KV)
|
1050
|
1050
|
1050
|
|
Usual Line Voltage (KV)
|
230
|
230
|
230
|
|
Leakage distance/in (mm)
|
198(5029)
|
198(5029)
|
198(5029)
|
|
Cantilever Strength/Ib (KN)
|
800(3.6)
|
1250(5.6)
|
2300(10.2)
|
|
Tensile Strength/Ib (KN)
|
20000(89)
|
25000(111.2)
|
40000(177.9)
|
|
Torsional Strength/in-Ib (N.m)
|
60000 (266.9)
|
90000(400.3)
|
20000(533.8)
|
|
Compression Strength /Ib (KN)
|
40000(177.9)
|
75000(333.6)
|
100000(444.8)
|
|
Critical Impulse Flashover Voltage, Positive (KV)
|
1210
|
1210
|
1210
|
|
Withstand Voltage
|
Low Frequency, Wet/KV
|
455
|
455
|
455
|
Impulse/KV
|
1050
|
1050
|
1050
|
|
Radio-Influence Voltage Data
|
Test Voltage to ground/kV
|
146
|
146
|
146
|
Maximum RIV at 1000 KHZ/µV
|
500
|
500
|
500
|
|
Shed diameter/in (mm)
|
9-7/8(251)
|
10-1/2(267)
|
10-7/8(276)
|
|
Bolt circle diameter/in (mm)
|
5(127)
|
5(127)
|
7(178)
|
|
(4)Tapped holes, size/in
|
5/8-11
|
5/8-11
|
3/4-11
|
|
Cap diameter-“C”/in (mm)
|
6-1/4(159)
|
6-1/4(159)
|
8-3/8(293)
|
|
Net Weight/Ib (kg)
|
265(117.9)
|
341(151.7)
|
424(188.6)
|
Relative Articles:
◆BS type Shackle insulator drawings and specifications
◆Spool insulator drawings and specifications
◆Ceramic line post insulator specifications